A1P Series Single Phase SCR Power Controllers
All Categories
The A1P is a proportional, infinitely variable power controller capable of delivering 0-97% of the applied line voltage to the directly connected electric heaters. The A1P will not control transformers or motors. This is accomplished by phase angle firing a pair of inversely connected SCR's. Modular construction allows for simple and solderless field serviceability. There are four field replaceable items:
- Printed circuit board
- Fuse
- Dual SCR package
- MOV (metal oxide varistor)
Unit of Measure
Items |
![]() A1P-12-30 A1P-12-30 Series Single Phase SCR Power Controller |
![]() A1P-12-40 A1P-12-40 Series Single Phase SCR Power Controller |
![]() A1P-12-60 A1P-12-60 Series Single Phase SCR Power Controller |
![]() A1P-12-80 A1P-12-80 Series Single Phase SCR Power Controller |
![]() A1P-12-100 A1P-12-100 Series Single Phase SCR Power Controller |
|||||
Voltage Designations | N/A 120 VAC 50/60 Hz | |||||||||
Load | N/A 30 AMPS | N/A 40 AMPS | N/A 60 AMPS | N/A 80 AMPS | N/A 100 AMPS | |||||
Output Voltage | N/A 0 to 97% of input voltage | |||||||||
Control Signal | N/A 4 to 20 mA at 5 volts DC, 250 Ohms | |||||||||
Linearity | N/A < 5% deviation | |||||||||
Response Time | N/A <12 mS (std unit, non soft start) | |||||||||
Cooling |
N/A
Convection: 30-100 amps Fan (120VAC): 150-1200 amps |
|||||||||
Thermostat | N/A 190 ºF (fan cooled units only) | |||||||||
Power Dissipation (Watts) | N/A 1.2 x maximum current | |||||||||
Net Weight | N/A 3.50 Pound | N/A 6 Pound | N/A 6 Pound | N/A 6 Pound | N/A 6 Pound | |||||
Shipping Weight | N/A 4 Pound | N/A 8 Pound | N/A 8 Pound | N/A 8 Pound | N/A 8 Pound | |||||
Minimum Wire Gauge (Copper Wire Only- 90 ºC Temp Wire) | N/A 10 AWG | N/A 8 AWG | N/A 6 AWG | N/A 4 AWG | N/A 3 AWG | |||||
Wire Lug Torque (90 ºC Temp Wire) | N/A 35 lb/in | N/A 40 lb/in | N/A 45 lb/in | N/A 45 lb/in | N/A 50 lb/in | |||||
Lug Size (90 ºC Temp Wire) | N/A 10 AWG | N/A 1/0 - 14 | N/A 1/0 - 14 | N/A 1/0 - 14 | N/A 1/0 - 14 | |||||
Soft Start | N/A S02-2 Seconds S05-5 Seconds S10-10 Seconds S20-20 Seconds | |||||||||
Current Limit | N/A CL- Current Limit CLP-Current Limit with Panel Mount Potentiometer | |||||||||
Voltage Limit | N/A VL-Standard 1 Turn PCB VL25-25 Turn PCB | |||||||||
Features |
N/A
|
|||||||||
Theory of Operation | N/A   The graphs below show phase angle fired voltage output on a 240V power line. The standard input signal (4-20 mA) is applied to the blue input terminal block, processed and fed to an optical coupler. The output of the optocoupler feeds the drive circuitry which is then fed to a pair of inversely connected SCR's. To obtain superior linearity, the line voltage is monitored and optically fed back to the input stage of the controller. An I²T fuse connected in series with the SCR's provides over current protection in the event of external wiring shorts, and or too large of a heater load. Additionally, a MOV (metal oxide varistor) is connected in parallel with the SCR's, providing voltage spike protection to the controller. | |||||||||
|